C-BUS TRAINING MANUAL - VOL 2
42
Function Action
On Set on
Off Set off
On/Off Alternate between set on and off
Dimmer Dim up or down, according to the dimmer function mode, which is set by
clicking the properties button. There are two dimmer modes, Toggle and
Memory.Toggle:A quick button press alternates between set on and off. The
dimmer switch does not remember a specific brightness level. A long button
press alternately dims up and down.Memory:A quick button press alternates
between a set to the previous dim level, and set off. A long button press
alternately dims up and down.
On Up A quick button press alternates between set to the previous dim level and
set off. A long button press dims up.
Off Down A quick button press alternates between set to the previous dim level and
set off. A long button press dims down.
Timer Initiate a count down timer, according to the timer function mode, which is
set by clicking the see properties button. A set off command is issued when
the timer expires. There are two timer modes, Toggle and Retrigger.Toggle:A
button press alternates between set on and set off. A button release starts
the timer.Retrigger:A quick button press issues a set on command and
starts (or restarts) the timer. A long button press issues a set off command.
Bell Press Set on until a button is released, then set off.
Dimmer Up Dim up.
Dimmer Down Dim down.
Soft Up A quick button press issues a ramp to preset level command (Recall 1). A
long button press dims up.
Soft Down A quick button press issues a ramp off command. A long button press dims
down.
Preset 1 A quick button press issues a set to preset level command (Recall 1). A long
button press ramps off.
Preset 2 A quick button press issues a set to preset level command (Recall 2). A long
button press ramps off.
Trigger 1 A quick (short) release triggers a Control Group Action Selector (stored in
Recall 1), which is set by clicking the see properties button. This can be
used to remotely trigger a scene in another C-Bus
®
unit. The Trigger 1 and
Trigger 2 functions are only selectable when the Application Address type is
set to Trigger Control.
Trigger 2 As per Trigger 1, but uses Recall 2 to store the Control Group Action
Selector.
Unused No action.
<Scene> Execute a Scene (this is covered in the Advanced Programming module).
A Scene is selectable on particular input unit types only, such as the Neo.
<Custom> Execute a customised function, using the parameters defined in the Button
(Key) Functions and Blocks tabs (covered in the Advanced Programming
module).
Table 1 – Functions which can be assigned to an input