Intelligent Building Series C-Bus Infrared Transmitter Installation Instructions
13.0 Electrical Specifications
Catalogue No. 5034NIRT
C-Bus Supply Voltage 15-36Vdc
Current Drawn 32mA
AC Input Impedance
50kΩ @ 1kHz
Electrical Isolation Rating 3.75kV RMS from C-Bus to mains
IR Ports 2
IR Port Output Voltage 5Vdc (maximum)
IR Port Output Current 20mA (maximum rated continuous output)
IR Port Terminals 2 x 3.5mm mono mini audio jacks
IR Code Formats Supported IR Carrier Frequencies 0 – 455kHz
Pulsed IR Code Formats (carrier-less)
IR Transmission Delay 200ms (minimum delay between consecutive
commands)
Communication Speed ~ 300 bits/sec (via C-Bus)
~ 10 kbits/sec (via 5100HSC)
C-Bus Unit Type PC_IRT2
C-Bus System Clock Software Selectable
C-Bus Network Burden Software Selectable
Maximum Number of Units on
a Single C-Bus Network
50 Units
C-Bus Input Terminals 0.2 – 1.5mm
2
(24-16AWG)
Shipping Weight 90gm
Storage Temperature Range -10 – 60
o
C
Operating Temperature Range 0 – 45
o
C
Operating Humidity Range 10 – 95% RH
Dimensions (L x W x H) 116 x 76 x 34mm (84mm Mounting Centres)
87 x 87 x 34mm (60mm Mounting Centres)
14.0 Mechanical Specifications
C-Bus
Unit
IR1
IR2
32
77
117
All dimensions are in millimeters.
No user serviceable parts inside.
Illustration shows Australian pattern
5034NIRT Only
© Copyright 2002 Clipsal Integrated Systems Pty Ltd Page 11