Intelligent Building Series C-Bus Infrared Transmitter Installation Instructions
3.0 Installation Instructions
A typical installation of the 5034NIRT C-Bus Infrared Transmitter is shown below:
3.1 Mounting Considerations
The E5034NIRT Unit is a British Standard Wall Plate, and may only be mounted
using deep style wall boxes (Clipsal Catalogue Number E157). Do not use the
shallow wall box (E157S).
All other units may be mounted using any of the standard Clipsal Australian
Pattern Wall Boxes and other Mounting Accessories.
It is recommended that the Unit be mounted close to the floor, and discreetly
located behind the control equipment. This will ensure a tidy installation.
3.2 Infrared Emitter Leads
The two IR output channels are connected by means of two 3.5mm mini audio
mono sockets located on the front of the Unit.
The recommended emitter leads to use with this product are the single head (cat.
no. 8050LD) or the dual head (cat. no. 8050/2LD) IR emitter leads.
The use of the recommended emitter leads will still allow the supplied remote for
the device to function as the emitter head is transparent to IR.
Extension leads may be used on the emitter leads of up to 50m of category 5 or
similar cable, such that the cable capacitance does not exceed 10nF.
The 3.5mm mini audio sockets are NOT isolated from C-Bus. Care must be
taken to ensure that these connector housings are not grounded, or otherwise
connected to an earth referenced voltage source (must be left floating).
© Copyright 2002 Clipsal Integrated Systems Pty Ltd Page 4